CONTROL MODES MENU
continued
4-20mA
page 3 of 3
NOTE: Signal alarms are non-latching and will clear automatically when the signal returns to specified operating range.
Alarms activate when settings are exceeded.
To
4-20mA
menu
Yes
No
High Signal Alarm
21.0 mA
Stop Pump on H ALM?
No
yes/no
set
Alarm on Low Signal?
Continued from previous page
yes/no
set
Yes
No
Low Signal Alarm
_ 3.0 mA
Stop Pump on L ALM??
No
yes/no
set
Alarm on High Signal?
yes/no
set
To
4-20mA
menu
Set high signal level. The
alarm activates when the
signal rises above the setting.
Select “Yes” to stop the pump in the
event of a low signal alarm. Select “No”
to allow the pump to continue running in
the event of a low signal alarm.
adjust
set
adjust
set
4-20mA
- Program Settings
- Alarm Settings
- Go to Main Menu
Select “Yes” to enable high signal alarm.
Select “No” to not enable the low signal alarm
and skip to the high signal
Alarm Settings.
Set low signal level. The
alarm activates when the
signal falls below the setting.
Select “Yes” to stop the pump in the
event of a high signal alarm. Select “No”
to allow the pump to continue running in
the event of a high signal alarm.
Select “No” to not enable the
high signal alarm and return to
the
4-20mA Control
menu.
Sets a value in a menu
NAVIGATION
Moves one step back in
a menu, when permitted
Moves up in a menu, toggles
between options, or increase a value
Moves down in a menu, toggles
between options, or decreases a value
Holding the or button causes the numbers to change rapidly.