S Series FW 3.02.02
www.stenner.com
12
GENERAL INFORMATION
continued
Mandatory Calibration
From the Configuration menu, select GPD/LPD Calibration, and enter your pump’s ACTUAL maximum flow rate
output. Refer to illustration below.
IMPORTANT!
The pump’s ACTUAL maximum flow rate entry:
・
Affects flow rate output displayed on the screen during operation in all modes.
・
Contributes to overall calculation of flow rate output in the PPM modes.
Program Applicable Pump Parameters
In Configuration menu, program applicable pump parameters, refer to chart below.
1
Enter max pump flow
_ _ 0.0 GPD
Calibration
- GPD/LPD Calibration
- Signal Calibration
- GO TO CONFIG MENU
Configuration
- Units
- Clock
- Calibration
adjust
set
2
Pump Parameters
Description
Control Mode
Display Brightness
Optimal setting is < 50% for extended periods.
All
Units
Default is Gallons; enter Liters, if preferred.
All
Clock
24-hr format. Enter current time of day and day of the week.
All
Leak Detect
Calibrate sensitivity to distinguish between water & your chemical.
All
Tube Timer
Enter number of hours you want pump to run before display
All
shows TUBE CHANGE.
Password
Program a password to prevent unauthorized changes to pump settings.
All
Output Relays
Three individual relays available; rated for 24VDC @ 50mA max.
All
Program communication for:
• S Series to back-up S Series
• S Series to another device
Signal Calibration
If factory settings are not sufficient,
calibrate the pump using a
4-20mA, 0-10VDC
process meter or powered transmitter.
Reset Totalizer
Option to reset the total tallied amount of water treated.
Pulse, Hall Effect, PPM
Modbus Setup
Modbus RTU over RS-485 capability; pump firmware 3.02.02 or higher
Manual, 4-20mA, 0-10VDC, Pulse
3
4
5
HOW TO GET STARTED SUMMARY
Select Mode of Operation
In Control Modes menu, select your mode of operation.
Program the Options
In your selected control mode, program the options relevant to your application.
Run the Pump