• Read these instructions.
• Keep these instructions.
• Heed all warnings.
• Follow all instructions.
• To reduce the risk of ignition don’t open or
disconnect the device when a potentially explosive
atmosphere is present. Keep the product tightly
closed when in operation.
• The equipment is certified for use in ambient
temperatures from -40°C to +60°C (from -40°F to
+140°F).
• Installation of this equipment shall be carried
out by suitably trained technical personnel in
accordance with the applicable code of practice
IEC/EN60079-14.
• The temperature of the surfaces of the device
is increased by exposure to direct sunlight.
The surface temperature class of the device
was determined only with ambient ambient
temperature, without taking into consideration
direct sunlight.
• Choose an installation surface that is strong
enough to sustain the weight of the device, also
bearing in mind particular environmental aspects,
such as exposure to strong winds.
• Since the user is responsible for choosing the
surface to which the unit is to be anchored, we
do not supply the fixing devices for attaching the
unit firmly to the particular surface. The installer is
responsible for choosing fixing devices suitable for
the specific purpose on hand. Use methods and
materials capable of supporting at least 4 times the
weight of the device.
• This device is remotely controlled and may change
position at any time. It should be installed so that
no one can be hit by moving parts. It should be
installed so that moving parts cannot hit other
objects and create hazardous situations.
• Make sure the appliance is securely anchored
before supplying power.
• A power disconnect device must be included
in the electrical installation, and it must be very
quickly recognizable and operated if needed.
• The connection compartment lid can be opened
only for cabling the device. The other lids must be
open from the manufacturer.
• Be careful not to use cables that seem worn or old.
• For technical services, consult only and exclusively
authorized technicians.
• Before proceeding with installation, check the
supplied material to make sure it corresponds
to the order specification by examining the
identification labels (4.2 Product marking, page
• This is a Class A product. In a domestic
environment this product may cause radio
interference. In this case the user may be required
to take adequate measures.
• To comply with the main supply voltage dips and
short interruption requirements, use a suitable
Uninterruptable Power Supply (UPS) to power the
unit.
Summary of Contents for EC-940-DUA Series
Page 2: ......
Page 4: ......
Page 87: ......
Page 88: ...MNTCMPXT_1824_EN R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 90: ......
Page 173: ......
Page 174: ...MNTCMPXT_1824_IT R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 176: ......
Page 259: ......
Page 260: ...MNTCMPXT_1824_FR R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 262: ......
Page 345: ......
Page 346: ...MNTCMPXT_1824_DE R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 347: ...RU EC 940 PTZ A EC 940 DUA PTZ...
Page 348: ......
Page 353: ...RU 7 MNTCMPXT_1824_RU 1 1 1 INFO 2 3 J1 6 5 19 1...
Page 354: ...RU 8 MNTCMPXT_1824_RU 40 C 60 C IEC EN60079 14 4 4 2 10...
Page 357: ...RU 11 MNTCMPXT_1824_RU 5 5 1 15A max 3mm 5 2...
Page 358: ...RU 12 MNTCMPXT_1824_RU 5 3 1 PTZ 1 2 1 1 2 2 IP 1 PTZ 1 2 1 1 2 2 1 CD 1 PTZ 1 2 1 3 6 2 2 5 4...
Page 363: ...RU 17 MNTCMPXT_1824_RU 6 3 15A max 3mm 80 C 10 C 3 4 NPT 01 02 03 02 01 03 12...
Page 376: ...RU 30 MNTCMPXT_1824_RU 6 21 STAHL 46 47 30mm 48 49...
Page 377: ...RU 31 MNTCMPXT_1824_RU 7 7 1 7 1 1 STAHL 7 1 2 7 1 3...
Page 378: ...RU 32 MNTCMPXT_1824_RU 8 De Ice 0 C 60 120 8 1...
Page 426: ...RU 80 MNTCMPXT_1824_RU 15 336 336 232 232 N 4 M10 N 4 M10 138 138 398 398 128 EC 940 PTZ A...
Page 427: ...RU 81 MNTCMPXT_1824_RU 453 453 232 232 N 4 M10 N 4 M10 138 138 398 398 129 EC 940 DUA...
Page 431: ......
Page 432: ...MNTCMPXT_1824_RU R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln...
Page 434: ......
Page 517: ......
Page 518: ...MNTCMPXT_1824_PT R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 519: ...KO EC 940 PTZ A EC 940 DUA PTZ...
Page 520: ......
Page 525: ...KO 7 MNTCMPXT_1824_KO 1 1 1 INFO 2 3 J1 6 5 19 1...
Page 526: ...KO 8 MNTCMPXT_1824_KO 40 C 60 C 40 F 140 F IEC EN60079 14 4 4 2 10 A UPS...
Page 529: ...KO 11 MNTCMPXT_1824_KO 5 5 1 15A 3mm 0 1 5 2...
Page 530: ...KO 12 MNTCMPXT_1824_KO 5 3 1 PTZ 1 2 1 1 2 2 IP 1 PTZ 1 2 1 1 2 2 1 CD 1 PTZ 1 2 1 3 6 2 2 5 4...
Page 535: ...KO 17 MNTCMPXT_1824_KO 6 3 15A 3mm 0 1 80 10 C 3 4 NPT 01 02 03 02 01 03 12...
Page 548: ...KO 30 MNTCMPXT_1824_KO 6 21 OR OR STAHL O 46 OR 47 30mm 48 49...
Page 549: ...KO 31 MNTCMPXT_1824_KO 7 7 1 7 1 1 STAHL 7 1 2 7 1 3...
Page 550: ...KO 32 MNTCMPXT_1824_KO 8 De Ice 0 C 60 120 8 1...
Page 579: ...KO 61 MNTCMPXT_1824_KO PC 117 118 9 7 2 1 WAN Setting IP IP 192 168 0 101 30 192 168 0 101 119...
Page 598: ...KO 80 MNTCMPXT_1824_KO 15 336 336 232 232 N 4 M10 N 4 M10 138 138 398 398 128 EC 940 PTZ A...
Page 599: ...KO 81 MNTCMPXT_1824_KO 453 453 232 232 N 4 M10 N 4 M10 138 138 398 398 129 EC 940 DUA...
Page 603: ......
Page 604: ...MNTCMPXT_1824_KO R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 605: ......
Page 606: ...MNTCMPXT_1824 MNTCMPXT_1824 R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...