Page 92
SITRANS LR 300 – INSTRUCTION MANUAL
7ML19985CL02
mmmmm
Tr
oubleshoot
ing
Operation Troubleshooting
Operating symptoms, probable causes, and resolutions.
Symptom
Cause
Action
display reads
level or target is out of range
• check specifications
• check P006
• increase range extension
P805
display reads
material build-up on antenna
• clean
• upgrade to purged antenna
• re-locate SITRANS LR 300
display reads
location or aiming:
• poor installation
• flange not level
• check to ensure nozzle is
vertical
• use P837
• check to ensure nozzle is
clean and free of internal
seams/welds
display reads
antenna malfunction:
• temperature too high
• physical damage
• excessive foam
• multiple echoes
• check P343
• use foam deflector or stilling
well
• relocate
• use a defoamer
• set P820 to 12 (First echo)
Reading does
not change, but
the level does
SITRANS LR 300 processing
wrong echo, i.e. vessel wall, or
structural member
• re-locate SITRANS LR 300
• check nozzle for internal burrs
or welds
• rotate unit 90
o
• use P837
Measurement is
consistently off
by a constant
amount
P006 not correct
P652 not correct
• Check distance from Flange
face to zero level (P006)
• Check offset value (P652) or
device tag
Screen blank
power error
• check nameplate rating
against voltage supply
• check power wiring or source
SITRANS LR 300.book Page 92 Monday, June 10, 2002 7:18 PM
Summary of Contents for SITRANS LR 300
Page 1: ...SITRANS LR 300 Instruction Manual ITRANS LR 30 July 2002 ...
Page 14: ...Page 12 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Specifications ...
Page 46: ...Page 44 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Start Up ...
Page 96: ...Page 94 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Troubleshooting ...
Page 136: ...Page 134 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Appendix VIII ...
Page 139: ......