P219 mA Output Fail-Safe
Used to set the mA Fail-Safe operation, independent of the Fail-Safe Material Level
(P071).
Installation Records Parameters (P340 to P346)
P340 Manufacture and Calibration Dates
Displays the year and month (yy-mm) for the following indexes:
P341 Run Time
Shows the accumulated number of days the SITRANS LR 300 has been operating.
P342 Power-On Resets
A counter that increments every time power is applied to the unit following an
interruption.
Values
0
Off (pre-set) mA output responds to Fail-Safe Material Level
1
HI
produces P213 (mA Output Maximum Limit)
2
LO
produces P212 (mA Output Minimum Limit)
3
HOLd
last known value is held until normal operation
resumes
Index
Data
01
manufacture date
02
calibration date
03
user date 1
Values (view only)
Display:
0.0 to 99999 (
days)
Note
:
User date can only be set remotely by a HART/Profibus master.