SITRANS LR 300 – INSTRUCTION MANUAL
Page 47
mm
mmm
Oper
ation
Analog Output
The SITRANS LR 300 can be programmed to provide an analog output (P200) of 4 to 20
mA, and for proportional or inverse span.
Programming
When the unit is put into PROGRAM mode, the analog output level holds its prior value
unless the mA output function is the common output or HART is the communication
protocol.
Run
The analog output responds in the following manner:
0 and 100% are percentage of full-scale reading (m, cm, mm, ft, in).
Volume
To program the unit for volume, set:
• operation (P001) to level
1
(see page 56)
• tank shape (P050) to a value other than
0
(see page 58)
• other volume parameters (P051 to P053) as required
To program the unit for ullage, set:
• operation (P001) to space
2
(see page 56)
• tank shape (P050) to a value other than
0
(see page 58)
• other volume parameters (P051 to P053) as required
Fail-Safe
When the Fail-Safe timer (P070) expires, the mA output responds as follows:
Fail-Safe Mode (071)
Status (4 - 20)
Status (20 - 4)
1 = high
22
2
2 = low
2
22
3 = hold
hold
hold
P001 = 1 (level)
P001 = 2 (space a.k.a. ullage)
P001 = 3 (distance)
SITRANS LR 300.book Page 47 Monday, June 10, 2002 7:18 PM
Summary of Contents for SITRANS LR 300
Page 1: ...SITRANS LR 300 Instruction Manual ITRANS LR 30 July 2002 ...
Page 14: ...Page 12 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Specifications ...
Page 46: ...Page 44 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Start Up ...
Page 96: ...Page 94 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Troubleshooting ...
Page 136: ...Page 134 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Appendix VIII ...
Page 139: ......