3.1.5.1
Flow Direction
Main flow direction related to direction ar‐
row on measuring tube (= forwards, posi‐
tive flow values)
+Direction
• +Direction,
• -Direction
3.1.5.2
Meas.Direction
Output of suppression of reverse flow
Affects all outputs, totalizers and display
forw.+rev.
• forward only,
• forw.+rev.
3.1.5.3
Hysteresis
Hysteresis of detection of flow direction in
% of full scale value
0.2 %
0 to 20 %
3.1.6
Low flow cut
Threshold for low flow cut in % of full scale
value 1, 2 or absolute value in flow unit 3
1 %
0 to 20 %
3.1.7
Noise filter
3.1.7.1
Fltr.Time Con.
Time constant τ for measured value attenu‐
ation; after a jump in
the measuring variable, the output meas‐
ured value reaches about 99% of the new
setpoint after 5*τ
Does not affect totalizers.
3.00 s
0.0 ... 200.0 s
3.1.7.2
Line Synchron.
Auto mode
Not available
3.1.7.3
Noise Suppress
Suppress Time
Suppress Limit
Values outside a tolerance range are evalu‐
ated for the duration of the blanking time
with high attenuation.
Time of effect of increased attenuation (0 s
= blanking off)
Tolerance range = floating a toler‐
ance value
0 s
0 %
0 ... 100
0 ... 100
3.1.8
Slurry mode
This is used when signals are severely im‐
paired, e.g. for media with a high solids
content or air locks
Off
• On
• Off
3.2
Total. Forw.
Totalizer forwards
3.2.1
Set forward
Reset totalizer to zero and stop or start
Cancel 1,2
Totalize 3
• Cancel 1,2,
• Reset+Stop,
• Reset+Start 1,2,
• Totalize 3
3.2.2
Engr. Unit
Engineering unit of volume
or
Engineering unit of mass When you select a
unit of mass, entry of the actual medium
density is mandatory (menu 3.1.4)
DN 2...12: l
DN >12: m3
• l, hl, m3, Ml, ft3, Gal,
MGal, ImpGal, MImpGal
• kg, t, g, lb
3.2.3
Alarm Limit
+1000000 l
-108 ... +108
3.3
Total. rev.
Totalizer reverse
3.3.1
Set reverse
Reset totalizer to zero and stop or start
Cancel 1,2
Totalize 3
• Cancel 1,2,
• Reset+Stop,
• Reset+Start 1,2,
• Totalize 3
Parameters
TRANSMAG 2 with MAG 911/E
Operating Instructions, 03/2021, A5E00102775-AC
97
Summary of Contents for SITRANS F TRANSMAG 2
Page 6: ...Table of contents TRANSMAG 2 with MAG 911 E 6 Operating Instructions 03 2021 A5E00102775 AC ...
Page 92: ...Dimension drawings TRANSMAG 2 with MAG 911 E 92 Operating Instructions 03 2021 A5E00102775 AC ...
Page 104: ...Parameters TRANSMAG 2 with MAG 911 E 104 Operating Instructions 03 2021 A5E00102775 AC ...
Page 126: ...Index TRANSMAG 2 with MAG 911 E 126 Operating Instructions 03 2021 A5E00102775 AC ...