0
b
a
-1
+1
①
Reverse
②
Forwards
③
Flow in % of range
Figure 8-3
Hysteresis flow direction
1. Hysteresis (3.1.5.3). The limit values (menu items 3.1.5.1 and 3.1.5.2) can have a hysteresis
added to prevent "fluttering" of the switching output.
This setting is made in % of the set full scale value in the menu item 3.1.5.3 "Hysteresis". If,
for example, the hysteresis is 1 %, the relay contact does not switch until a flow of -1% of the
full scale value and returns to the original position at a flow of +1% of the full scale value.
Table 8-2
Switching status of the relay for selected signal type
- Contact closes:
a →
Relay contact closed
b →
Relay contact open
- Contact opens:
a →
Relay contact open
b →
Relay contact closed
• Low flow cut, menu item 3.1.6
This parameter determines the switching point for low flow cut-off. The low flow cut prevents
flow being measured in the lower range (e.g. fluctuating liquid columns at a standstill). The
low flow cut-off affects: display, totalizers, analog output and pulse frequency output as well
as HART and PROFIBUS communication.
– In devices with HART communication, the value of the low flow is related percentage-wise
to the upper range value (menu item 3.1.2).
– In devices with PROFIBUS communication, the absolute value must be entered in the
selected unit of flow (menu item 3.1.1).
• Filter time constant, menu item 3.1.7.1
The jump response can be suppressed in this menu item. This may be necessary depending
on the application, for example in the case of fast changing flows to keep the display value
or analog value stable.
Functions
8.4 Function Group Measuring Functions
TRANSMAG 2 with MAG 911/E
60
Operating Instructions, 03/2021, A5E00102775-AC
Summary of Contents for SITRANS F TRANSMAG 2
Page 6: ...Table of contents TRANSMAG 2 with MAG 911 E 6 Operating Instructions 03 2021 A5E00102775 AC ...
Page 92: ...Dimension drawings TRANSMAG 2 with MAG 911 E 92 Operating Instructions 03 2021 A5E00102775 AC ...
Page 104: ...Parameters TRANSMAG 2 with MAG 911 E 104 Operating Instructions 03 2021 A5E00102775 AC ...
Page 126: ...Index TRANSMAG 2 with MAG 911 E 126 Operating Instructions 03 2021 A5E00102775 AC ...