The more than 300 parameters including address (Slot and Index), format, value range, start
value and attributes are stored in an object list "Obj80C4.rtf" which will be provided on request.
Note
Acyclic operation with SIMATIC PDM
We recommend using the SIMATIC PDM software package and a PC (compatible with industry
standard) or a programming unit for acyclic operation.
B.4
Input Data (from Slave to Master)
Input data are process data (measured values) which are transmitted from the device to the
master in the following format:
Every measured value consists of 5 bytes which are composed of a floating point value
corresponding with IEEE - 754 (4 bytes) and the correspondent measured value status (1 byte).
In the PROFIBUS telegram, the measured value is transmitted first and then the corresponding
status.
Table B-1
Measured value format
Byte
Bit
No.
7 (MSB)
6
5
4
3
2
1
0 (LSB)
1
VZ
E
2
7
E
2
6
E
2
5
E
2
4
E
2
3
E
2
2
E
2
1
2
E
2
0
M
2
-1
M
2
-2
M
2
-3
M
2
-4
M
2
-5
M
2
-6
M
2
-7
3
M
2
-8
M
2
-9
M
2
-10
M
2
-11
M
2
-12
M
2
-13
M
2
-14
M
2
-15
4
M
2
-9
M
2
-9
M
2
-9
M
2
-9
M
2
-9
M
2
-9
M
2
-9
M
2
-9
VZ: sign: 0 positive, 1 negative E: Exponent M: Mantissa
B.5
Status bytes
Status bytes
The status bytes consist of three components:
• Quality (the MSBs 6 and 7):
Describes the basic quality of the corresponding measured value
• Substatus (bits 2 to 5):
Differentiates the quality of the corresponding measured value
• Limits (the LSBs 0 and 1):
Indicate exceeding of the limit value
Profibus Communication
B.5 Status bytes
TRANSMAG 2 with MAG 911/E
108
Operating Instructions, 03/2021, A5E00102775-AC
Summary of Contents for SITRANS F TRANSMAG 2
Page 6: ...Table of contents TRANSMAG 2 with MAG 911 E 6 Operating Instructions 03 2021 A5E00102775 AC ...
Page 92: ...Dimension drawings TRANSMAG 2 with MAG 911 E 92 Operating Instructions 03 2021 A5E00102775 AC ...
Page 104: ...Parameters TRANSMAG 2 with MAG 911 E 104 Operating Instructions 03 2021 A5E00102775 AC ...
Page 126: ...Index TRANSMAG 2 with MAG 911 E 126 Operating Instructions 03 2021 A5E00102775 AC ...