Menu code Device func‐
tion,
Parameters
Description
Factory setting
Setting options
1.2
Multi-Display
Simultaneous display of two measuring var‐
iables
(actual meas‐
ured value line 1)
(actual meas‐
ured value line 2)
• Menu 1.1.2
• Menu 1.1.3
1.3
Flow
Flow value
(actual meas‐
ured value)
1.4
Totalizer
Flow quantity since totalizer start; volume
or mass, depending on selected unit (menu
3.1.1)
(actual totalizer
reading)
1.4.1
Total. forward
Forward flow only
(actual totalizer
reading)
1.4.2
Total. rev.
Reverse flow only
(actual totalizer
reading)
1.4.3
Total. net
Flow difference forward - reverse
(actual totalizer
reading)
1.4.4
Set (all)
Reset all totalizers simultaneously to zero
and stop or start;
(separate setting of totalizers, see menu
3.2.1, 3.3.1, 3.4.1)
Cancel
• Reset+Stop,
• Reset+Start
• Cancel
1.5
Flow Velocity
Flow velocity in measuring tube in m/s
(actual meas‐
ured value)
1.6
Frequency
Calculated frequency value for actual flow
in Hz
(actual meas‐
ured value)
1.7
Analog Out 1, 2
Calculated current value for actual flow in
mA
(actual meas‐
ured value)
Diagnostics
Table A-2
Function group diagnostics parameters
2.1
Device status
Device status, error messages
("OK" or error
messages)
2.2
Electr.Check
Supervision of electrodes in sensor
Inactive
• Active
• Inactive
2.3
EmptyTube Det.
Time interval for immersion check of elec‐
trodes or deactivation of immersion check.
In case of insufficient immersion of both
electrodes in conductive medium, ’Tube
empty’ is reported under device status.
Inactive
• Inactive
• 15 s
• 30 s
• 60 s
• 120 s
• 300 s
2.4
Device Test
Self Test
Check device status (duration approx. 60s)
2.4.2
Display Test
Visual check of local display
2.5
Simulation
Parameters
TRANSMAG 2 with MAG 911/E
94
Operating Instructions, 03/2021, A5E00102775-AC
Summary of Contents for SITRANS F TRANSMAG 2
Page 6: ...Table of contents TRANSMAG 2 with MAG 911 E 6 Operating Instructions 03 2021 A5E00102775 AC ...
Page 92: ...Dimension drawings TRANSMAG 2 with MAG 911 E 92 Operating Instructions 03 2021 A5E00102775 AC ...
Page 104: ...Parameters TRANSMAG 2 with MAG 911 E 104 Operating Instructions 03 2021 A5E00102775 AC ...
Page 126: ...Index TRANSMAG 2 with MAG 911 E 126 Operating Instructions 03 2021 A5E00102775 AC ...