Parameter description
62
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.D Communication Parameters
Code
Description
Setting range
Default
Modify
Modbus
Address
Fd.00
RS 485
0: Disabled
RS485
1: Enabled
RS485
0
О
0E00H
Fd.01
Local address
1 ~ 247
1
о
0E01H
Fd.02
Baud rate setup
1: 1200BPS
2: 2400BPS
3: 4800BPS
4: 9600BPS
5: 19200BPS
6: 38400BPS
3
о
0E02H
0E03H
Fd.03
Parity bit setup
1: Even parity
check
2: Odd parity
check
3: No parity
check
0
о
Fd.04
Communication
timeout
detection
duration
Range: 0.0—
100.0s
0: No timeout
detection
Others:
Timeout
detection
duration
0.0s
о
0E04H
Fd.05
Response delay
duration
0~500ms
5ms
о
0E05H
Fd.06
Communication
Freq. setting
coefficient
0.0~200.0%
100.00 %
о
0E06H
Fd.07
Communication
interrupt
detection mode
0: Time
interval
between 2
packets
receiving.
1: Time
interval of
0005H Add.
data writing
0
о
0E07H