Installation
13
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
4.6 SINAMICS V50 Standard configuration of control circuit terminals
Type
Termin
Terminal function Technical specification
Digital
input
X1
X3
Multi-functional
input terminals 1 -3
Optical-isolator input Frequency
range: 0 - 200Hz
Voltage range: 0 - 24V
X4
X5
Multi-functional
input or Single pulse
input 4, 5
Multi-functional input: same as X1 -
X3
Single Pulse input: 0.1Hz - 50kHz
Voltage range: 0 - 24V
COM
Multi-functional
input terminals
common end
Internal isolated with GND
Digital
output
24V
24V
24V±5%, Maximum load :200mA,
with overload and short circuit
protection
Y1
Open collector
output 1
Optical-isolator output maximum
output current: 50mA
Output voltage range: 0 - 24V
DO
Open collector or
high-speed pulse
output
Output frequency: 0 - 50kHz
Can be used as the normal open
collector.
COM
Open collector
output common
end
Internal isolated with GND
Analog
input
10V
Analog input
reference voltage
Open circuit voltage up to 11V;
Internal isolated with COM;
Maximum load 30mA, with overload
and short circuit protection
AI1
Analog input
channel 1
Input Voltage range: 0 - 10V
Input impedance: 100kOhm
AI2
Analog input
channel 2
Input Voltage range: 0 - 10V
Input impedance: 100kOhm
Input current range: 0-30mA
Current input impedance: 500Ohm,
0 - 20mA or 0 - 10V analog input can
be selected through DIP switch
SW2
GND
Analog grounding Internal isolated with COM
Analog
output
AO1
Analog output 1
0/4 - 20mA: Allow output impedance
200-500Ohm
0-10V: Allowed output impedance
>10kOhm.