![Siemens SINAMICS V50 Operating Instructions Manual Download Page 40](http://html.mh-extra.com/html/siemens/sinamics-v50/sinamics-v50_operating-instructions-manual_385614040.webp)
Parameter description
39
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.3 Vector Control Parameters
Code
Description
Setting range
Default
Modify
Modbus
Address
F3.36
Synchronous
motor flux
weaken mode
0: Flux weaken
mode is invalid
1: Flux weaken
mode is valid
0
о
0424H
F3.37
Max flux
weaken
current
0~100.0%
50%
о
0425H
F3.38
Flux weaken
regulation
proportional
coefficient
0~3000
1500
о
0426H
F3.39
Flux weaken
regulation
integration
coefficient
0~3000
1500
о
0427H
F3.40
Synchronous
motor low
speed Min.
current
0~100%
30%
о
0428H
F3.41
Synchronous
motor low
speed carrier
frequency
1.0~16.0KHz
2.0KHz
о
0429H
F3.42
Synchronous
motor Min
-100.0~100.0%
8.0%
о
042AH
F3.43
V/F Start
switching
frequency
0~50.00Hz
0.00Hz
о
042BH
F3.44
Synchronous
motor position
evaluating low
speed filter
2~100
40
о
042CH
F3.45
Synchronous
motor position
evaluating
high speed
filter
2~100
15
о
042DH
Summary of Contents for SINAMICS V50