Parameter description
46
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.6
Input terminals
Code
Description
Setting range
Default
Modify Modbus
Address
F6.19
AI2 Max. input
corresponding
setup
-200.0~200.0%
100.00%
о
0713H
F6.20
AI2 input filter
time
0.01~50.00s
0.05s
о
0714H
F6.21
PULSE Min.
input
0.00~F6.23
0.00kHz
о
0715H
F6.22
PULSE Min.
input
corresponding
setup
-200.0%~200.0%
0.00%
о
0716H
F6.23
PULSE Max.
input
F6.21~50.00kHz
50.00kHz
о
0717H
F6.24
PULSE Max.
input
corresponding
setup
-200.0%~200.0%
100.00%
о
0718H
F6.25
Pulse filter time
0.01~50.00s
0.05s
о
0719H
F6.26
Terminal
up/down initial
increment
0.00~10.00Hz
0.01Hz
о
071AH
F6.27
Freq. ref.2
datum
0: Max. freq.
1: Freq. ref.1
0
о
071BH
F6.28
Delay duration
of X1 terminal
close
0.0~100.0s
0.0s
о
071CH
F6.29
Delay duration
of X1 terminal
open
0.0~100.0s
0.0s
о
071DH
F6.30
Delay duration
of X2 terminal
close
0.0~100.0s
0.0s
о
071EH
F6.31
Delay duration
of X2 terminal
open
0.0~100.0s
0.0s
о
071FH
F6.32
Pos. and Neg.
logic terminal
X 1
Pos. logic of Xi
terminal:
Be valid while
connecting between Xi
and COM.
0000
X
0720H