Parameter description
59
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.B Fixed Length
Code
Description
Setting range
Default Modify
Modbus
Address
Fb.00
Preset length
0~6553.0
0
о
0C00H
Fb.01
Actual length
0~6553.0
0
*
0C01H
Fb.02
Pulses number
per unit
0.1~6553.0
100
о
0C02H
6.C Protection and Fault Parameters
Code
Description
Setting range
Default
Modify
Modbus
Address
FC.00
Motor overload
protection mode
0: Disabled
1: Common
motor (with low
speed
compensation)
2: Variable
frequency
motor (without
low speed
compensation)
1
X
0D00H
FC.01
Electro thermal
protection value
20~110%
100%
О
0D01H
FC.02
Overload
Pre-alarm
detection level
30.0~200.0%
160%
О
0D02H
FC.03
Overload
Pre-alarm
detection time
0.0~80.0s
60.0s
О
0D03H
FC.04
Current
amplitude limit
0: Invalid
1: Acc./Dec.
valid; Constant
speed invalid
2: Valid all the
time
2
О
0D04H
0D05H
FC.05
Current
amplitude limit
level
80.0~200.0%
160.0%
О
FC.06
Over voltage stall
function
0: Invalid
(Recommended
if braking
1
X
0D06H