![Siemens SINAMICS V50 Operating Instructions Manual Download Page 51](http://html.mh-extra.com/html/siemens/sinamics-v50/sinamics-v50_operating-instructions-manual_385614051.webp)
Parameter description
50
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.7
Output terminal
Code
Description
Setting range
Default
Modify
Modbus
Address
F7.13
Preset Counting
arrival value
0~9999
0
о
080DH
F7.14
Preset Timing
arrival value
0.0 ~ 6553.0s
0.0s
о
080EH
F7.16
AI1 compare
threshold 1
0.00~10.00V
0.00V
о
0810H
F7.17
AI1 compare
threshold 2
0.00~10.00V
0.00v
о
0811H
F7.18
Analog compare
hysteresis error
0.00~30.00V
0.20V
о
0812H
F7.19
AO1 output
selection
0: NULL
1: Running freq.
(0~max
frequency)
2: Setting freq.
(0~max
frequency)
3: Output current
(0~2 times of
drive rated
current)
4:
Output voltage
(0 ~ Max
Voltage)
5:
PID setup (0~
10V)
6:
PID feedback
(0~ 10 V)
7:
Calibrating
signal (5V)
8: Output torque
(0 ~ 2 times of
motor rated
torque)
9: Output power
(0 ~ 2 times of
drive rated
power)
10: Bus voltage
(0~1000V)
1
о
0813H
F7.20
AO2 output
selection
0
о
0814H
F7.21
DO output
selection
0
о
0815H
Summary of Contents for SINAMICS V50