![Siemens SINAMICS V50 Operating Instructions Manual Download Page 31](http://html.mh-extra.com/html/siemens/sinamics-v50/sinamics-v50_operating-instructions-manual_385614031.webp)
Parameter description
30
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.1 Start and stop control (F1)
Code
Description
Setting range
Default
Modify Modbus
Address
F1.00
Start mode
0: Start directly
1: DC injection
brake first and then
start at start freq.
2: Speed tracking
and start
0
о
0200H
F1.01
Start freq.
0.10~60.00Hz
0.50Hz
о
0201H
F1.02
Start freq.
hold time
0.0~10.0s
0.0s
о
0202H
F1.03
DC brake
current at
start
0.0~100.0% rated
current
0.00%
о
0203H
F1.04
DC brake
time at start
0.0~30.0s
0.0s
о
0204H
F1.05
Acc./Dec.
mode
0: Linear
1: S-curve
0
о
0205H
F1.06
Time of S-
curve nitial
stage
10.0 50.0% (Acc./ Dec.
time)
F1.06+F1.07<90%
30.00%
о
0206H
F1.07
Time of S-
curve rising
stage
10.0~80.0% (Acc./
Dec. time)
F1.06+F1.07<90%
40.00%
о
0207H
F1.08
Stop mode
0: Deceleration to
stop 1: Coast to stop
2: DeceleDC
braking
0
X
0208H
F1.09
DC brake
trigger
frequency at
stop
0.00 550.0Hz
0.00Hz
0
0209H
F1.10
DC brake
waiting time
at stop
0.00~10.00s
0.00s
0
020AH
F1.11
DC brake
current at
stop
0.0~100.0% rated
current
0.00%
0
020BH
F1.12
DC brake
time at stop
0.0~30.0s
0.0s
0
020CH