Parameter description
60
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.C Protection and Fault Parameters
Code
Description
Setting range
Default
Modify
Modbus
Address
resistor
mounted)
1:
Valid for
Acc/Dec.
2: Valid all the
time
FC.07
Overvoltage point
for Acc./Dec.
suspend
110.0~150.0%
(Bus voltage)
380V:140%
X
0D07H
220V:120%
FC.08
Input phase loss
detection
1~100% (100%
correspond to
800V)
20%
X
0D08H
FC.09
Input phase loss
detection delay
time
2~255s
10s
X
0D09H
FC.10
Output phase loss
detection
0: Invalid
1: Valid
1
о
0D0AH
FC.11
Terminal close
fault detection
0: Invalid
1: Valid
1
о
0D0BH
FC.12
Fault auto reset
times
0
—
10, “0” means
auto reset is
disabled. Only 3
faults have auto
reset function
0
X
0D0CH
FC.13
Fault auto reset
interval
0.1~20.0s/time
5.0s
X
0D0DH
FC.14
Under-voltage
fault treatment
0: No treatment
1: Auto reset at
power recovery
2: Auto run at
power recovery
(Auto run time
interval is
F1.16)
0
о
0D0EH
FC.15
Fast current limit
50.0%~100.0%
(100% means this
function is
disabled.)
Depends
on model
о
0D0FH
FC.16
Fast current limit
time
0.01~1.00s
0.10s
о
0D10H