![Siemens SINAMICS V50 Operating Instructions Manual Download Page 54](http://html.mh-extra.com/html/siemens/sinamics-v50/sinamics-v50_operating-instructions-manual_385614054.webp)
Parameter description
53
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.
8
PID Parameters
Code
Description
Setting range
Default Modify Modbus
Address
6: MAX(AI1, AI2)
7: MIN(AI1, AI2)
F8.02
Analog PID
digital setup
0.0 999.9
50
о
0902H
F8.03
Analog closed
loop measuring
range
1.0 999.9
100
о
0903H
F8.04
PID action
direction
0: Positive
1: Negative
0
о
0904H
F8.05
PID proportional
gain 1 (KP1)
0.1-9.9
1
о
0905H
F8.06
PID integration
time 1
0~100s
3s
о
0906H
F8.07
PID differential
time 1
0.00~1.00s
0.00s
о
0907H
F8.08
PID proportional
gain 2 (KP2)
0.1-9.9
1
о
0908H
F8.09
PID integration
time 2
0.0~100.0s
10.0s
о
0909H
F8.10
PID differential
time 2
0.00~1.00s
0.00s
о
090AH
F8.12
PID parameter
switching
Deviation 1
0.0 999.9
20
о
090CH
F8.13
PID parameter
switching
Deviation 2
0.0 999.9
80
о
090DH
F8.14
PID delay time
constant
0.0~100.0s
0.0s
о
090EH
F8.15
Deviation limit
0.0 999.9
0.2
о
090FH
F8.16
PID output
positive limit
0.0~600.0Hz
50.00Hz
о
0910H
F8.17
PID output
negative limit
0.00 550.0Hz
0.00Hz
о
0911H
F8.18
PID preset freq.
0.00 550.0Hz
0.00Hz
X
0912H
F8.19
Hold time of PID
preset
frequency
0.0~3600s
0.0s
X
0913H
F8.20
Enable
dormancy
0: Disabled
1: Enabled
0
X
0914H
Summary of Contents for SINAMICS V50