Commissioning
4.7 Restoring the factory setting
Inverter with CU240B-2 and CU240E-2 Control Units
92
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
4.7
Restoring the factory setting
The inverter is reset to the delivery condition by restoring the parameters to the factory
setting, with the exception of the following parameters.
Note
The reset operation is not applied to parameters p0014, p0100, p0201, p0205 or the
communication parameters. Motor parameters p0300 ... p0311 are suitably preassigned for
the power unit.
Restoring the factory settings using STARTER
● Go online with STARTER, see Establishing an online connection between the PC and
converter (going "online") (Page 80).
● In STARTER, click on the button
.
Resetting to factory setting with BOP-2
● In the "Options" menu, select the "DRVRESET" entry
● Confirm the reset using the OK key.
Resetting parameters when the safety functions are active
In order to reset the safety function parameters together with all other parameters of the
inverter, proceed as follows:
● Go online with STARTER.
● Open the safety functions screen and deactivate the safety functions.
● Go offline with STARTER.
● Switch off the Control Unit power supply for approximately 10 seconds (Power ON
Reset).
● Go online with STARTER.
● Reset the Control Unit to the factory setting.