Functions
7.4 Setpoint sources
Inverter with CU240B-2 and CU240E-2 Control Units
162
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Table 7- 5
Extended setup of motorized potentiometer
Parameter
Description
P1030
Configuration of the MOP, parameter value with four independently adjustable bits
00 … 03 (factory setting 0110 bin)
Bit 00: Save setpoint after switching off motor
0: After the motor is switched on, p1040 is specified as the setpoint
1: Setpoint is saved after the motor is switched off and set to the saved value once it
is switched on
Bit 01: Configure ramp-function generator in automatic mode (1-signal via BI: p1041)
0: No ramp-function generator in automatic mode (ramp-up/-down time = 0)
1: With ramp-function generator in automatic mode
In manual mode (0-signal via BI: p1041) the ramp-function generator is always active
Bit 02: Configure initial rounding
0: No initial rounding
1: With initial rounding. The initial rounding is a sensitive way of specifying small
setpoint changes (progressive reaction when keys are pressed).
Bit 03: Store setpoint in power-independent manner
0: No power-independent saving
1: Setpoint is saved in the event of a power failure (bit 00 = 1)
P1035
Signal source to increase setpoint (factory setting 0)
Automatically pre-assigned during commissioning, e.g. with the button on the
Operator Panel
P1036
Signal source to reduce setpoint (factory setting 0)
Automatically pre-assigned during commissioning, e.g. with the button on the
operator panel
P1037
Maximum setpoint (factory setting 0 rpm)
Automatically pre-assigned during commissioning
P1038
Minimum setpoint (factory setting 0 rpm)
Automatically pre-assigned during commissioning
P1039
Signal source to invert minimum and maximum setpoints (factory setting 0)
P1041
Signal source to switch from manual to automatic (factory setting 0)
P1042
Signal source for setpoint in automatic mode (factory setting 0)
P1043
Signal source to accept set value (factory setting 0)
E.g. command to switch on motor
P1044
Signal source for set value (factory setting 0)
For more information about the motorized potentiometer, see the List Manual (function
diagram 3020 and the parameter list).