
Technical data
10.3 Technical data, Power Modules
Inverter with CU240B-2 and CU240E-2 Control Units
270
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Table 10- 9 PM240 frame size GX, 3-ph. 380 V AC… 480 V, ± 10 %
Order number
Without filter
6SL3224-0BE41-3UA0
6SL3224-0BE41-6UA0
6SL3224-0BE42-0UA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
160 kW
297 A
302 A
200 kW
354 A
370 A
250 kW
442 A
477 A
Values based on High Overload
● HO power
● HO input current
● HO output current
132 kW
245 A
250 A
160 kW
297 A
302 A
200 kW
354 A
370 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight
3.9 kW
355 A
360 l/s
95 ... 240 mm
2
14 Nm
176 kg
4.4 kW
400 A
360 l/s
120 ... 240 mm
2
14 Nm
176 kg
5.5 kW
630 A
360 l/s
185 ... 240 mm
2
14 Nm
176 kg