Commissioning
4.6 Back-up the settings and transfer
Inverter with CU240B-2 and CU240E-2 Control Units
86
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
4.6
Back-up the settings and transfer
4.6.1
External data backup and series commissioning
After commissioning, your settings are saved in the inverter so that they are protected
against power failure.
In addition, you should also save the parameters on a storage medium outside the inverter:
By backing up your data on an external storage medium, if the inverter develops a defect,
your settings will not be lost.
You have three different options for externally backing up data (upload):
1.
Memory card
2.
PC/PG with STARTER
3.
Operator Panel
Series commissioning
Series commissioning means the commissioning of several identical drives in the following
steps:
1.
Commission the first inverter.
2.
Upload the parameters of the first inverter to the storage medium outside the inverter.
3.
Download the parameters from the storage medium to a second or additional inverter.
Note
The control unit to which the parameters are transferred must be of the same type and
have the same or a higher firmware version as the source control unit (the same 'type'
means the same MLFB).
For further information, refer to the following sections.
4.6.2
Backing up and transferring settings using STARTER
Backing up the inverter settings on PC/PG (upload)
● Go online with STARTER
.
● Click on the button "Load project to PG": .
● To save data in the PG (computer), click on .
Transferring settings from the PC/PG into the inverter (download)
● Go online with STARTER.
● Click on the button "Load project to target system": .
● To save data in the converter, click on "Copy RAM to ROM" .