Commissioning
4.6 Back-up the settings and transfer
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
87
4.6.3
Backing up and transferring settings using BOP-2
Transferring parameters from the inverter to the operator panel (upload)
● Start data transfer in the menu "OPTIONS" - "TO BOP".
● Wait until the BOP-2 signals that data transfer has been completed.
Note
Data transfer can can take several minutes.
Transferring parameters from the operator panel to the inverter (download)
● Start data transfer in the menu "OPTIONS" - "FROM BOP".
● Wait until the BOP-2 signals that data transfer has been completed.
4.6.4
Saving setting on memory card
The memory card is a removable, non-volatile flash memory for all inverter parameters.
We recommend that you use one of the memory cards with the following order numbers:
● MMC (order number 6SL3254-0AM00-0AA0)
● SD (order number 6ES7954-8LB00-0AA0)
If you wish to use other SD or MMC memory cards, then you must format the memory card
as follows:
● MMC: Format FAT 16
– Insert the card into your PC's card reader.
– Start a "command prompt" on your PC and enter the following: format x: /fs:fat
(x: Drive code of the memory card on your PC.)
● SD: Format FAT 32
– Insert the card into your PC's card reader.
– Start a "command prompt" on your PC and enter the following: format x: /fs:fat32 (x:
Drive code of the memory card on your PC.)