Connecting
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
34
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Notes for installing Power Modules
The Power Module must not be installed horizontally.
&RUUHFW
,QFRUUHFW
Devices that could impede the flow of cooling air must not be installed in this area. Make
sure that the ventilation openings for the cooling air for the inverter are not covered and that
the flow of cooling air is not obstructed.
Installing additional components
Depending on the application, additional line reactors, filters, braking resistors, brake relays
etc., may also be used.
Please observe the mounting and installation instructions supplied with these components!
3.3.2
Dimensions, hole drilling templates, minimum clearances, tightening torques
Note
With the exception of inverters in the 160 kW … 250 kW power range, the CU240B-2 und
CU240E-2 increase the inverter's total depth by 40 mm and by a further 30 mm if using an
IOP.