Alarms, faults and system messages
9.3 List of warnings
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
249
9.3
List of warnings
Table 9- 7
The most important warnings
Number
Cause
Remedy
A01028
Configuration error
Explanation: Parameterization on the memory card has been created with a
different type of module (order number, MLFB)
Check the module parameters and recommission if necessary.
A01590
Motor maintenance interval
lapsed
Carry out maintenance and reset the maintenance interval (p0651).
A01900
PROFIBUS: Configuration
telegram faulty
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
A01920
PROFIBUS: Cyclic connection
interrupt
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
with cyclic operation.
A03520
Temperature sensor fault
Check that the sensor is connected correctly.
A05000
A05001
Power Module overtemperature Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
A07012
I2t Motor Module
overtemperature
Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
A07015
Motor temperature sensor
alarm
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
A07321
Automatic restart active
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is
automatically switched back on.
A07850
A07851
A07852
External alarm 1 … 3
The signal for "external alarm 1" has been triggered.
Parameters p2112, p2116 and p2117 determine the signal sources for the
external alarm 1… 3.
Remedy: Rectify the cause of this alarm.
A07903
Motor speed deviation
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
A07910
Motor overtemperature
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
A07927
DC braking active
Not required
A07980
Rotary measurement activated Not required
A07981
No enabling for rotary
measurement
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).