Alarms, faults and system messages
9.5 List of faults
Inverter with CU240B-2 and CU240E-2 Control Units
258
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Number Cause
Remedy
F30015
Motor cable phase failure
Check the motor cables.
Increase the ramp-up or ramp-down time (P1120).
F30027
Time monitoring for DC link pre-
charging
Check the supply voltage on the input terminals.
Check the line voltage setting (P0210).
You will find additional information in the List Manual and in the online help of STARTER.
Table 9- 12 Faults which can only be acknowledged by switching off and on again
Number Cause
Remedy
F01000
Software fault in CU
Replace CU.
F01001
Floating Point Exception
Switch CU off and on again.
F01015
Software fault in CU
Upgrade firmware or contact hotline.
F01018
Power-up aborted more than once After this fault has been output, the module is booted based on factory
settings.
Remedy: Back up factory setting with p0971=1. Switch CU off and on
again. Recommission the inverter.
F01040
Parameters must be saved
Save parameters (P0971).
Switch CU off and on again.
F01044
Loading of memory data card
defective
Replace memory card or CU.
F01105
CU: Insufficient memory
Reduce number of data records.
F01205
CU: Time slice overflow
Contact the Hotline.
F01250
CU hardware fault
Replace CU.
F01512
An attempt has been made to
establish an conversion factor for
scaling which is not present
Create scaling or check transfer value.
F01662
CU hardware fault
Switch CU off and on again, upgrade firmware or contact hotline.
F30022
Power Module: Monitoring U
CE
Check or replace the Power Module.
F30052
Incorrect Power Module data
Replace Power Module or upgrade CU firmware.
F30053
Error in FPGA data
Replace the Power Module.
F30662
CU hardware fault
Switch CU off and on again, upgrade firmware or contact hotline.
F30664
CU power up aborted
Switch CU off and on again, upgrade firmware or contact hotline.
F30850
Software fault in Power Module
Replace Power Module or contact hotline.