Commissioning
4.3 Commissioning with factory settings
Inverter with CU240B-2 and CU240E-2 Control Units
62
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
4.3.3
Pre-assignment of the inputs and outputs
Terminal strip factory settings
Digital inputs
Terminal Abbreviation
Parameter Factory setting
Meaning of the factory setting
5
DI0
P0701
1 or 0
ON/OFF1
6
DI1
P0702
12 or 0
Direction reversal
7
DI2
P0703
9
Fault acknowledgment
8
DI3
P0704
15
Fixed frequency selector bit 0 (direct) [P1001]
16
DI4
P0705
16
Fixed frequency selector bit 1 (direct) [P1002]
17
DI5
P0706
17
Fixed frequency selector bit 2 (direct) [P1003]
Digital outputs (relay outputs)
Terminal Abbreviation
Parameter Factory setting
Meaning of the factory setting
18
NC
19
NO
20
COM
DO0
P0730
52.3
Drive fault active
21
NO
22
COM
DO1
P0731
52.7
Drive alarm active
23
NC
24
NO
25
COM
DO2
P0732
52.2
Operation enabled
Analog inputs
Terminal Abbreviation
Parameter Factory setting
Meaning of the factory setting
3
AI0+
4
AI0-
AI0
P0756 [0]
4
Set bipolar voltage input
-10 V … +10 V DC
in addition to parameterizing DIP switch on CU housing.
In the factory setting, analog input 0 supplies the speed setpoint.
10
AI1+
11
AI1-
AI1
P0756 [1]
4
Set bipolar voltage input
-10 V … +10 V DC
in addition to parameterizing DIP switch on CU housing.