Connecting
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
49
Shielding with shield connection kit:
Shield connection kits are available for all Power
Module frame sizes (you will find more information
in Catalog D11.1). The cable shields must be
connected to the shield connection kit through the
greatest possible surface area using shield clamps.
Shielding without shield connection
kit:
EMC-compliant shielding can also be implemented
without an optional shield connection kit. In this
case, you must ensure that the cable shields are
connected to the ground potential through the
largest possible surface area.
Braking resistor connection:
The braking resistor is connected using a shielded
cable. Using a clamp, the shield should be
connected to the mounting plate or to the shield
connection kit through a good electrical connection
and through the largest possible surface area.