Functions
7.11 Switchover between different settings
Inverter with CU240B-2 and CU240E-2 Control Units
232
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Table 7- 43 Command data set changeover using parameters P0810 and P0811.
Status of binector
P0810
0
1
0
1
Status of binector
P0811
0
0
1
1
The command
data set that is
presently active
has a gray
background.
&'6
&'6
&'6
CDS2 is only
available when
P0170 = 3 or 4
&'6
CDS3 is only
available when
P0170 = 4
Selected
parameter index
0
1
2
3
Fieldbus as
setpoint source:
The speed
setpoint is
specified via the
fieldbus.
Analog input as
setpoint source:
The speed
setpoint is
specified via an
analog input
-
-
Examples
Fieldbus as
command source:
The motor is
switched on/off via
the fieldbus.
Digital inputs as
command source:
The motor is
switched on/off via
digital inputs
-
-
Note
Command data sets can be switched over in the "ready for operation" and "operation" state.
The switchover time is approx. 4 ms.
Table 7- 44 Parameters for switching the command data sets
Parameter
Description
P0810
1st control command for switching the command data sets
Example: When P0810 = 722.0, the system switches from command data set 0 to
command data set 1 via digital input 0.
P0811
2nd control command for switching the command data sets
r0050
Displaying the number of the CDS that is currently active
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the Parameter Manual.