EMC-compliant installation of Power Modules in degree of protection IP20
The EMC-compliant installation of power modules is shown in the following diagram using
two examples.
①
Line supply connection
②
Motor connection
③
Metal mounting plate (unpainted and with a good electrical conductivity)
④
Cable clamps for a good conductive electrical connection through a large surface area
between the shield and mounting plate or shield connection kit.
⑤
Shielded motor cable
⑥
Shield connection kit
⑦
Unshielded cable for Power Modules with integrated line filter.
Shielded cable to connect a Power Module to an external line filter
Figure 3-9
Power Module shielding