Commissioning
4.3 Commissioning with factory settings
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
61
Table 4- 1
Command and setpoint sources
Parameter
Description
P0700 = 2 or 6
Select the command source
2: Digital inputs (P0701 … P0709) (factory setting for CUs without PROFIBUS interface)
6: Fieldbus (P2050 … P2091), (factory setting for CUs with PROFIBUS DP interface)
P1000 = 2 or 6
Select the setpoint source
2: Analog setpoint (factory setting for CUs without PROFIBUS DP interface)
6: Fieldbus (factory setting for CUs with PROFIBUS DP interface)
Table 4- 2
Factory settings of additional important parameters
Parameter Factory setting
Meaning of the factory
setting
Name of the parameter and comments
P0010
0
Ready to be entered
Drive, commissioning parameter filter
P0100
0
Europe [50 Hz]
IEC/NEMA motor standard
IEC, Europe
NEMA, North America
Note: This parameter cannot cannot be changed in FW4.3.
P0300
1
Induction motor
Motor type selection (induction motors / synchronous
motor)
P0304
400
[V]
Rated motor voltage (in accordance with the rating plate in
V)
P0305
depends on the
Power Module
[A]
Rated motor current (in accordance with the rating plate in
A)
P0307
depends on the
Power Module
[kW/hp]
Rated motor power (in accordance with the rating plate in
kW/hp)
P0308
0
[cos phi]
Rated motor power factor (in accordance with the rating
plate in cos 'phi'). If P0100=1, 2, then P0308 has no
significance.
P0310
50
[Hz]
Rated motor frequency (in accordance with the rating plate
in Hz)
P0311
1395
[rpm]
Rated motor speed (in accordance with the rating plate in
rpm)
P0335
0
Non-ventilated: Shaft-
mounted fan in the motor
Motor cooling type (specify the motor cooling system)
P0625
20
[°C]
Motor ambient temperature
P0640
200
[A]
Current limit (of the motor)
P0970
0
Locked
Reset drive parameters (restore to the factory settings)
P1080
0
[rpm]
Minimum speed
P1082
50
[rpm]
Maximum speed
P1120
10
[s]
Ramp-function generator, ramp-up time
P1121
10
[s]
Ramp-function generator, ramp-down time
P1300
0
V/f control with linear
characteristic
Open-loop/closed-loop control operating mode