Fail-Safe Blocks
Fail-Safe Systems
8-34
A5E00085588-03
TIMEOUT Parameter
The input TIMEOUT cannot be interconnected and must be assigned a constant
value. See "Monitoring Safety-Related Communication Between CPUs".
Error Handling
If a connection partner receives an invalid safety frame (e.g.: due to a check value
error (CRC) or watchdog error) or doesn’t receive a valid safety frame within the
TIMEOUT monitoring time, the outputs ERROR and SUBS_ON are set and the
substitute values are output. An error code is displayed at the output RETVAL.
Note
Once communication has been set up without errors, compliance with the assigned
monitoring time (TIMEOUT parameter) is checked.
Communication between the connection partners is reestablished. The data
received with valid safety frames is not applied to the outputs (= reintegrated) until
the input ACK_REI had a rising edge (e.g. via F_QUITES).
The block sets the output ACK_REQ to indicate that acknowledgment is required.
In the event of an error that is critical to safety, the system function SFC F_CTRL
is called. This records the event in the Diagnostic Buffer and requests a switch to
the reserve CPU if the error occurred only on the master CPU. For non-redundant
systems or a common-cause error occurring in both CPUs, the shutdown logic can
be configured to either disable the erred F-run-time group or the entire Safety
Program.
Error Information in Diagnostic Buffer
Error Code (W#16#...)
Description
75DAH
Error in the safety data format (error due to online modification
of the Safety Program or internal CPU fault)
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...