Safety
Fail-Safe Systems
7-18
A5E00085588-03
•
The specified I/Os must be checked in the case of the following fail-safe
blocks:
Fail-Safe Block
I/O
Description
F_CYC_CO
MAX_CYC
Maximum permissible
F cycle time
F_SENDBO, F_RCVBO
F_SENDR, F_RCVR
TIMEOUT
Monitoring time during
communication between F-
CPUs
F_R_R, F_R_BO
TIMEOUT
Monitoring time during
communication between F-
run-time groups
F_M_DI8
F_M_DI24
F_M_DO10
F_M_DO8
F_M_AI6
TIMEOUT
Monitoring time for
PROFIsafe communication
with F-I/O
F_M_DI8
F_M_DI24
F_M_DO10
F_M_DO8
F_M_AI6
LADDR
LADDR_R
Logical address of the
module (SM1)
Logical address of the
redundant module (SM2)
F_M_AI6
MODE_00 to MODE_05
Measurement range coding
in the case of an analog
input module
F_CH_DI,
F_CH_DO, F_CH_AI
ACK_NEC
Acknowledgment required
for reintegration
F_LIM_HL
QH
1: Upper limit violated
F_LIM_LL
QL
1: Lower limit violated
F_RS_FF
Q
Output
F_SR_FF
Q
Output
F_CTUD
CV
Current count value
Switched output parameters are marked with an asterisk (*) on the printout.
Checking the Signatures
Overall signature: After the program has been downloaded to the CPU (see the
sections entitled "Downloading the Whole Safety Program" and "Downloading
Changes"), you have to compare the overall signature of the program in the CPU
with the overall signature in the accepted printout. In the case of S7 FH systems,
you have to make this comparison for both CPUs.
Signatures and initial-value signatures of the F-Blocks: The signatures and
initial-value signatures of all the fail-safe blocks must be identical with those in
Annex 1 of the certificate report. When you use newly created F-Block types, you
must carry out this comparison for all the F-Blocks called in the F-Block type.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...