Downloading a Safety Program
After compilation you can download the CFC program to the PLC. Depending on
whether or not safety mode is activated, you can download the entire Safety
Program or just changes to the Safety Program as follows:
Downloading
CPU in
STOP
CPU in RUN, Safety
Mode Active
CPU in RUN, Safety
Mode Inactive
Of the entire Safety
Program
Possible
Not possible
Not possible
Of changes to the
standard program
Not
possible
Possible
Possible
Of changes to the
Safety Program
Not
possible
Not possible
Possible
Prerequisites
•
Before the entire Safety Program is downloaded, there should be a memory
reset of the CPU if it contains an old Safety Program.
•
The hardware configuration data of the station is downloaded to the CPU.
•
The user program is compiled without error.
•
You have access rights to the PLC.
•
There is an online connection between the CPU and your programming
device/ES.
Rules for Downloading
•
The Safety Program can only be downloaded from CFC, not from SIMATIC
Manager.
•
In the S7 FH Systems, the two CPUs must have the same (F) user program.
Both CPUs have either a RAM or a flash EPROM memory card.
•
When an accepted Safety Program is downloaded, you must check the overall
signature after downloading in the same way as you must after acceptance
(see "Checking the Overall Signatures" in the section entitled "Initial
Acceptance of a Safety Program").
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...