Configuration
Fail-Safe Systems
4-12
A5E00085588-03
Adding F-I/O’s via CIR
To add a new F-I/O to your System follow these steps:
•
Configure the new F-I/O within HWCONFIG according to the manual, “How to
Modify the System during Operation wth CiR (handle it like a standard module)
•
Calculate the Monitoring Time for this F-Module (see “Calculate the Monitoring
Time for Communication between the F-CPU and the F-I/O“) and use it to
update the Monitoring Time for this F-Module in HWCONFIG.
•
Modify your safety program (add safety logic, channel driver and module driver
for this module)
•
Deactivate safety mode (see “Deactivating Safety Mode“)
•
Download your safety program
•
Download your configuration via CiR
•
Activate safety mode (see “Activating Safety Mode“)
Deleting F-I/O‘s via CiR
To delete an already existing F-I/O from your System follow these steps:
•
Delete the F-I/O within HWCONFIG according to the manual, “How to Modify
the System during Operation with CiR“ (handle it like a standard module)
•
Modify your safety program (delete safety logic, channel driver and module
driver for this module)
•
Deactivate safety mode (see “Deactivating Safety Mode“)
•
Download your safety program
•
Download your configuration via CiR
•
Activate safety mode (see “Activating Safety Mode“)
Note
You can only delete an existing F-I/O via CiR if the module was added to the
system via CiR.
Changing of an exisiting configuration of an F-I/O is not possible.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...