Programming
Fail-Safe Systems
5-70
A5E00085588-03
The differences are described as follows:
Text
Meaning
Deleted
Block only exists in the source
Added
Block only exists in the comparison object
Task changed from ’Task1’ to ’Task2’
Block in another task/priority class
Run-time group changed from ’Group1’ to
’Group2’
Block in another run-time group
Instance DB changed from ’I-DB1’ to ’I-
DB2’
Block has another instance DB
Run position changed
Block in different run position within the run-time
group
Interface changed
Number of parameters changed
Interconnection changed from ’Connect1’
to ’Connect2’
Interconnection of a parameter changed
Result of the Comparison of the Safety Blocks (online program)
If the “Compare with: field selects the online program, only the Block View
difference output is shown. There are two additional viewing options available by
use of the check boxes:
•
Show unconnected F-FB input parameter differences
•
Filter F-System checksums
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...