Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-137
Errors in Runtime Communications – Protocol Fault
Error Code (W#16#...)
Cause
Remedies
75DCH
This fault results in disabling of the F-run-time
group that contains the faulted F-FB and
possibly disabling of the entire Safety Program
(depending upon the configuration of FULL_SD
input of the FB F_SHUTDN , either Full
Shutdown or Partial Shutdown). The fault due
to an internal failure of the RAM or F-CPU.
•
Restart the Shutdown logic.
-or-
•
Stop and ColdStart F-CPU.
-or-
•
Full Download of the
complete program to F-CPU.
-or-
•
Replace the F-CPU.
Error Detected in F_PLK – Program/Data Flow Control Error Before Output Blocks
Error Code (W#16#...)
Cause
Remedies
75E1H
Error processing F_CYC_CO, internal CPU fault
Error processing F_TEST, internal CPU fault
Error processing F_TESTC, internal CPU fault
Error due to online modification of the Safety
Program or internal CPU fault
•
Restart the Shutdown logic.
-or-
•
Stop and ColdStart F-CPU.
-or-
•
Full Download of the
complete program to F-CPU.
-or-
•
Replace the F-CPU.
Error Detected in F_PLK_O – Program/Data Flow Control Error After Output Blocks
Error Code (W#16#...)
Cause
Remedies
75E1 H
Error due to online modification of the Safety
Program or internal CPU fault
•
Restart the Shutdown logic.
-or-
•
Stop and ColdStart F-CPU.
-or-
•
Full Download of the
complete program to F-CPU.
-or-
•
Replace the F-CPU.
Error Detected in F_CYC_CO – Exceeding of the F Cycle Time by...
Error Code (W#16#...)
Cause
Remedies
75E1H
Power failure,
Internal CPU fault
•
Restart the Shutdown logic.
-or-
•
Stop and ColdStart F-CPU.
-or-
•
Full Download of the
complete program to F-CPU.
-or-
•
Replace the F-CPU.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...