Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-133
Output
Cause
Remedies
n = 1: Diagnostic information for module SM1
n = 2: Diagnostic information for redundant module SM2
Output
Cause
Remedies
Byte 1 (in the case of F_M_DI8 and F_M_DI24 only)
•
Bit 0: Discrepancy error on channel 0 of
SMn
Check sensor
•
...
•
Bit 7: Discrepancy error on channel 7 of
SMn
Byte 2 (in the case of F_M_DI24 only)
•
Bit 0: Discrepancy error on channel 8 of
SMn
•
...
•
Bit 7: Discrepancy error on channel 15 of
SM1
Byte 3 (in the case of F_M_DI24 only)
•
Bit 0: Discrepancy error on channel 16 of
SM1
•
...
•
Bit 7: Discrepancy error on channel 23 of
SMn
n = 1: Diagnostic information for module SM1
n = 2: Diagnostic information for redundant module SM2
Note
In byte 0 of DIAG_1/2, the most recent error information remains stored until a new
error occurs, even if the error has already gone.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...