Programming
Fail-Safe Systems
A5E00085588-03
5-45
Procedure
1.
Create the CFC chart in a separate S7 program assigned to an F-capable
CPU.
2.
Open the chart you want.
3.
Choose the Chart > Compile > Chart as Block menu command. A dialog box
for entering the block properties appears.
4.
Enter the properties of the new block type. Select the options "Compile for PLC
- S7 400" and "Optimize Code for - Downloading Changes in RUN Mode" and
confirm with OK.
Result: A new block type is created that can be used in safety programs.
5.
Insert the new block type in a Safety Program and test it there.
6.
Accept the Safety Program of the new F-Block type.
Using a New Block Type in the Safety Program
If you use a fail-safe block of a newly created type, you must recompile the Safety
Program and download the whole program or the changes to the CPU.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...