Fail-Safe Blocks
Fail-Safe Systems
8-138
A5E00085588-03
Error Code (W#16#...)
Cause
Remedies
75E1H
Maximum permissible F cycle time exceeded or
internal CPU fault
•
Restart the Shutdown
logic.
-or-
•
Stop and ColdStart F-
CPU.
-or-
•
Full Download of the
complete program to F-
CPU.
-or-
•
Replace the F-CPU.
-or-
•
Increase the cycle time of
the OB3x containing your
F-run-time Group
experiencing the
maximum cycle time
exceeded
-or-
•
Move functionality out of
the OB3x to another
OB3x. This includes
standard and F-Blocks
that are running within
said F- run-time the OB3x.
Error Detected in F_TEST – Command Test
Error Code (W#16#...)
Cause
Remedies
75E1H
Internal CPU fault
•
Restart the Shutdown
logic.
-or-
•
Stop and ColdStart F-
CPU.
-or-
•
Full Download of the
complete program to F-
CPU.
-or-
•
Replace the F-CPU.
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...