Programming
Fail-Safe Systems
A5E00085588-03
5-63
Changing a Fail-Safe Block I/O
1.
Activate test mode for the chart in CFC using the Test > Test Mode menu
command.
2.
Open the sheet view of the F-Block.
3.
Select the block I/O that you want to change, and open Object Properties with
a double-click, for example.
Result: The "Select Structure Element" dialog box appears.
4.
Double-click the DATA structure element in the "Select Structure Element"
dialog box.
Result: The "Properties – Inputs/Outputs" dialog box appears.
5.
Enter the desired value in the "Value" text box and confirm with "OK".
Summary of Contents for SIMATIC S7 F