Fail-Safe Blocks
Fail-Safe Systems
8-104
A5E00085588-03
I/Os
Name
Data Type
Explanation
Default
Inputs:
CU
F_BOOL
Up-counting input
0
CD
F_BOOL
Down-counting input
0
R
F_BOOL
Reset input (R dominates over
LOAD)
0
LOAD
F_BOOL
Load input (LOAD dominates
over CU and CD)
0
PV
F_INT
Preset value
0
Name
Data Type
Explanation
Default
Outputs:
QU
F_BOOL
Status of the up counter
QU has the value
– 1 if CV >= PV
– 0, otherwise
0
QD
F_BOOL
Status of the down counter
QD has the value
– 1 if CV <= 0
– 0, otherwise
0
CV
F_INT
Current count value
0
Note
If, when you create the program, you preset the CV output in CFC with an initial
value of < 0 or > 0, the counter is incremented or decremented as of this value.
Note that the initial values of output parameters do not appear in the printout of the
CFC chart. They must be checked in the printout of the safety program.
Error Handling
In the event of an error that is critical to safety, the system function SFC F_CTRL
is called. This records the event in the Diagnostic Buffer and requests a switch to
the reserve CPU if the error occurred only on the master CPU. For non-redundant
systems or a common-cause error occurring in both CPUs, the shutdown logic can
be configured to either disable the erred F-run-time group or the entire Safety
Program.
Error Information in Diagnostic Buffer
Error Code (W#16#...)
Description
75DAH
Error in the safety data format of the input CU, CD, R, LOAD
or PV (error due to online modification of the Safety Program
or internal CPU fault)
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...