Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-107
8.10.3 F_TON
Function
The block delays a rising edge by the time PT.
A rising edge at the input IN results in a rising edge at the output Q after the time
PT has elapsed. Q remains set until the input IN changes to 0.
If the input IN changes to 0 before PT has elapsed, Q remains at 0.
The output ET indicates the time that has elapsed since the last rising edge at the
input IN, but only up to the value of the input PT. ET is reset if the input IN changes
to 0.
If PT < 0, the outputs Q and ET are reset.
Timing Diagram
scasc
Q
IN
PT
ET
PT
PT
Startup Characteristics
In the first cycle after a cold or warm restart or in the case of a first call, the timer is
reset.
I/Os
Name
Data Type
Explanation
Default
Inputs:
IN
F_BOOL
Start input
0
PT
F_TIME
Length of the delay
T#0 ms
Outputs:
Q
F_BOOL
Pulse output
0
ET
F_TIME
Elapsed time
T#0 ms
Summary of Contents for SIMATIC S7 F
Page 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Page 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Page 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Page 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Page 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Page 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Page 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Page 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Page 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Page 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Page 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...