8 Using the Data Record Interface
139
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
Byte
Meaning
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Parameter 30/30B
Parameter 31/31B
169
P3
P2
P1
P0
P3
P2
P1
P0
170
Flag 1
171
Flag 2
Flag 1
Flag 2
Bit Number
Meaning
Bit Number
Meaning
0
CONFIG_OK
0
PERIPHERY_OK
1
LDS_0
1
DATA_EXCHANGE_ACTIVE
2
AUTO_ADDR_ASSIGN
2
OFFLINE
3
AUTO_ADDR_AVAIL
3
AUTO_ADDR_ENABLE
4
CONFIG_MODE
4
Ground short
5
NORMAL_MODE
5
EPROM_OK
6
APF
6
reserved
7
OFFLINE_READY
7
reserved
In the table, the rows of the flags whose values change the mode of the AS-i
master (CONFIG_MODE, AUTO_ADDR_ENABLE) are shown in white.
The values of the other flags (gray in the table) have no significance for the
’Set_LPS_PCD_PP_Flags’ call and cannot be modified on the AS-i master with
this call..
The meaning of the flags is the same as in the “Get_LPS_LAS_LDS_LPF_Flags”
job, Section 8.2.1.4).