8 Using the Data Record Interface
160
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
8.2.2.9
Write_Parameter_String
Meaning
With AS-i slaves with profile 7.4, this call can be used to send a parameter string to
the AS-i master that then forwards this to the specified AS-i slave address.
The call transfers a parameter string with a maximum of 220 bytes. The actual
number of parameter bytes to be sent to the AS-i slave is calculated by the AS-i
master from byte 2. The maximum number of parameter bytes is 220.
The remaining information in the string is not evaluated by the AS-i master and is
passed on to the AS-i slave transparently. As long as the string transfer is active,
there is no user/analog data exchange with the addressed AS-i slave.
Structure of the RecordDataWrite service − Index 28
Byte
Meaning
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Version_hi = 0x00
1
Version_lo = 0x00
2
Number of string bytes
3
String byte 1
4
String byte 2
...
...
221
String byte 219 (may be irrelevant)
222
String byte 220 (may be irrelevant)