8 Using the Data Record Interface
126
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
Table 8-5
AS-i Slave Calls
Name
Function
Index
(deci-
mal)
Data in the send /
receive buffer
Description
Set_Permanent_Parameter
Write
3
Parameter value
Get_Permanent_Parameter
Read
4
Parameter value
Write_Parameter
Write
5
Parameter value
Read_Parameter
Read
6
Parameter value
Set_Permanent_Configuration
Write
8
Configuration
Get_Permanent_Configuration
Read
9
Configuration
Read_Actual_Configuration
Read
11
Configuration
Read_I/O_Configuration
Read
33
I/O configuration
Read_ID-Code
Read
34
ID code
Read_Extended_ID-Code_1
Read
24
ID1 code
Read_Extended_ID
−
Code_2
Read
35
ID2 code
Read_Status
Read
80
Status of the AS-i
slave (error flags)
Get_Write_Parameter_Echo
Read
81
Parameter echo
value
Write_Analog_Output_Data
Write
82
Analog output data of
the AS-i slave
Read_Analog_Output_Data
Read
83
Analog input data of
the AS-i slave
Read_AS-i_Slave_Errorcounters
Read
98
Error counters
Read_and_delete_AS-i_Slave_Errorcoun–
ters
Read
99
Error counters
Table 8-6
AS-i Slave Calls for Slaves Complying with AS-i Specification V3.0 (CTT1, CTT2)
Name
Function
Index
(decim
al)
Data in the send /
receive buffer
Description
Read_Parameter_String
Read
27
Parameter string
Write_Parameter_String
Write
28
Parameter string
Read_Diagnostic_String
Read
29
Diagnostic string
Read_Identification_String
Read
30
ID string
Write_CTT2_String
Write
31
CTT2 string
Read_CTT2_String
Read
31