Wiring
6.8 Front connector for the I/O modules
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
67
Components of a front connector for I/O modules with shield contact element
The shielding bracket, the power supply element, and the shielding clamp are included in the
scope of delivery for the analog and technology modules.
The following figure shows the components of a front connector:
①
Shield clamp
⑥
Power supply element
②
Cable sheathing removed (approx. 20
mm)
⑦
Shielding bracket
③
Strain relief (cable tie)
⑧
Supply lines
④
Signal cables
①
+
⑦
Shield contact
⑤
Front connectors
Figure 6-6
Components of a front connector for I/O modules with shield contact element
Preparing front connectors for I/O modules with shield contact element
Watch video sequence (
1.
Remove the connection separator from the lower part of the connector (Figure 1).
2.
Insert the power supply element (Figure 2).
3.
Insert the shielding bracket from below into the front connector until it latches into place
(Figure 3).