Installation
5.3 Installing the power supply module
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
45
5.3
Installing the power supply module
Introduction
The power supply module is optional for the ET 200MP distributed I/O system, and can be
deployed as needed.
The power supply module increases the power on the backplane bus and thus permits the
use of additional modules.
Requirements
The mounting rail is installed.
An I/O module located before the power supply (PS) module has a U connector inserted at
back right.
Tools required
Screwdriver with 4.5 mm blade
Installing the power supply module
1.
Place the U connector at the back right on the power supply (PS) module (see following
picture).
2.
Install the power supply module on the mounting rail.
3.
Pivot the power supply module towards the back.
Figure 5-4
Installing the power supply module
4.
Open the front cover.
5.
Disconnect the power cable connector from the power supply module.
6.
Fasten the power supply module (torque 1.5 Nm).
7.
Insert the already wired-up power cable connector into the power supply module.
For a description on how to wire the power cable connector refer to the section Connecting
Summary of Contents for simatic ET 200MP
Page 4: ...Preface ET 200MP Distributed I O System 4 System Manual 01 2013 A5E03723484 01 ...
Page 8: ...Table of contents ET 200MP Distributed I O System 8 System Manual 01 2013 A5E03723484 01 ...
Page 118: ...Service Support ET 200MP Distributed I O System 118 System Manual 01 2013 A5E03723484 01 ...
Page 126: ...Index ET 200MP Distributed I O System 126 System Manual 01 2013 A5E03723484 01 ...