Wiring
6.5 Connecting supply voltage to the interface module
ET 200MP Distributed I/O System
58
System Manual, 01/2013, A5E03723484-01
6.5
Connecting supply voltage to the interface module
Introduction
The supply voltage of the interface module is supplied via a 4-pole cable connector, that is
located on the front of the interface module.
Power supply unit
You must only use SELV/PELV type power supply units with protective extra-low voltage
with safe electrical isolation (max. 28.8 V DC).
The required power of the power supply unit depends on the power consumption of the
connected components.
Connection for supply voltage
The connections have the following meaning:
/
/
0
0
①
Mass of the supply voltage
②
Mass of the supply voltage for looping (permitted value 10 A)
③
+ 24 V DC of the supply voltage for looping (permitted value 10 A)
④
Spring release
⑤
+ 24 V DC of the supply voltage
1L+ and 2L+ as well as 1M and 2M are internally bridged.
Figure 6-3
Supply voltage connection
The maximum conductor cross-section is 1.5 mm
2
. The cable connectors offer you the option
of looping the supply voltage uninterrupted, even when it is unplugged.
Requirements
●
Only wire the cable connector when the supply voltage is turned off.
●
Follow the wiring rules (Page 57).
Tools required
3 to 3.5 mm screwdriver
Summary of Contents for simatic ET 200MP
Page 4: ...Preface ET 200MP Distributed I O System 4 System Manual 01 2013 A5E03723484 01 ...
Page 8: ...Table of contents ET 200MP Distributed I O System 8 System Manual 01 2013 A5E03723484 01 ...
Page 118: ...Service Support ET 200MP Distributed I O System 118 System Manual 01 2013 A5E03723484 01 ...
Page 126: ...Index ET 200MP Distributed I O System 126 System Manual 01 2013 A5E03723484 01 ...